Generatorsteuerung. Start bei schwacher Batterie erkannt und Run ON Stop Delay Timer
Connect the external battery bank to AECM107 terminals A+ and B- and select "External Battery Control" mode by using the "External / Engine Battery Monitor Selector" Button. When external battery bank voltage drops below 12Vdc the BVS will automatically start and run the engine. The BVS will stop requesting the AECM107 controller to run when the external battery bank voltage becomes equal or higher than 12.8Vdc. The stop delay timer will continue to run the generator if it was initially set up and powered by the Red DIP switch #1. All operating modes and stopping conditions for a running generator are valid as indicated in the description above (please refer to "start from remote wired switch" description). While the BVS is requesting the AECM107 to run, it is possible to stop the engine e.